Pilt on illustreeriv
|
Repeater Power Supply MINIMCR-SL-RPS-I-I, 1pc/pck, Phoenix Kood:
2864422
Hind (indikatiivne)
€ 245,00
/tk
(€ 303,80 /tk KM-ga)
Tootja
:
Saadavus:
21 päeva
|
Kaal:
0.0756 kg/tk
|
|
|
|
|
|
Repeater Power Supply MINIMCR-SL-RPS-I-I, 1pc/pck, PhoenixNote
Utilization restriction
|
EMC: class A product, see manufacturer's declaration in the download area
|
Dimensions
Width
|
6.2 mm
|
Height
|
93.1 mm
|
Depth
|
101.2 mm
|
Ambient conditions
Ambient temperature (operation)
|
-20 °C ... 60 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Maximum altitude
|
≤ 2000 m
|
Permissible humidity (operation)
|
5 % ... 95 % (non-condensing)
|
Degree of protection
|
IP20
|
Noise immunity
|
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
|
Input data
Description of the input
|
Current input (sensor circuit)
|
Number of inputs
|
1
|
Current input signal
|
4 mA ... 20 mA (repeater power supply and isolator operation)
|
|
0 mA ... 20 mA (isolator operation)
|
Max. input current
|
28 mA
|
Input resistance current input
|
approx. 50 Ω
|
Transmitter supply voltage
|
UB - max. 4.5 V for load 0 mA ... 20 mA
|
Transmitter supply voltage range
|
14.7 V DC ... 25.5 V DC
|
Output data
Output name
|
Current output
|
Number of outputs
|
1
|
Current output signal
|
4 mA ... 20 mA (repeater power supply and isolator operation)
|
|
0 mA ... 20 mA (isolator operation)
|
Max. output current
|
28 mA
|
Load/output load current output
|
≤ 500 Ω (I = 20 mA)
|
Ripple
|
< 20 mVrms (at 500 Ω)
|
Transmission Behavior
|
1:1 to input signal
|
Power supply
Nominal supply voltage
|
24 V DC
|
Supply voltage range
|
19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
|
Power consumption
|
< 900 mW (at 24 V DC and in repeater power supply operation)
|
|
< 600 mW (at 24 V DC and in isolator operation)
|
Connection data
Connection method
|
Screw connection
|
Stripping length
|
12 mm
|
Screw thread
|
M3
|
Conductor cross section solid
|
0.2 mm² ... 2.5 mm²
|
Conductor cross section flexible
|
0.2 mm² ... 2.5 mm²
|
Conductor cross section AWG
|
26 ... 12
|
General
No. of channels
|
1
|
Maximum transmission error
|
≤ 0.2 % (of final value)
|
Transmission error, typical
|
≤ 0.1 % (of final value)
|
Maximum temperature coefficient
|
< 0.01 %/K
|
Temperature coefficient, typical
|
< 0.002 %/K
|
Limit frequency (3 dB)
|
approx. 100 Hz
|
Step response (10-90%)
|
approx. 3.5 ms
|
Protective circuit
|
Transient protection
|
Electrical isolation
|
Basic insulation according to EN 61010
|
Overvoltage category
|
II
|
Degree of pollution
|
2
|
Rated insulation voltage
|
50 V AC/DC
|
Test voltage, input/output/supply
|
1.5 kV (50 Hz, 1 min.)
|
Electromagnetic compatibility
|
Conformance with EMC directive
|
Noise emission
|
EN 61000-6-4
|
Noise immunity
|
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
|
Color
|
green
|
Housing material
|
PBT
|
Mounting position
|
any
|
Assembly instructions
|
To bridge the supply voltage, the DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used. It can be snapped onto a 35 mm DIN rail according to EN 60715.
|
Fire protection for rail vehicles (DIN EN 45545-2) R22
|
HL 1 - HL 2
|
Fire protection for rail vehicles (DIN EN 45545-2) R23
|
HL 1 - HL 2
|
Fire protection for rail vehicles (DIN EN 45545-2) R24
|
HL 1 - HL 2
|
EMC data
Designation
|
Electromagnetic RF field
|
Standards/regulations
|
EN 61000-4-3
|
Typical deviation from the measuring range final value
|
10 %
|
Designation
|
Fast transients (burst)
|
Standards/regulations
|
EN 61000-4-4
|
Typical deviation from the measuring range final value
|
10 %
|
Designation
|
Conducted interferences
|
Standards/regulations
|
EN 61000-4-6
|
Typical deviation from the measuring range final value
|
10 %
|
Standards and Regulations
Electromagnetic compatibility
|
Conformance with EMC directive
|
Noise emission
|
EN 61000-6-4
|
Connection in acc. with standard
|
CUL
|
Standards/regulations
|
EN 61000-4-2
|
Designation
|
Electromagnetic RF field
|
Standards/regulations
|
EN 61000-4-3
|
|
EN 61000-4-4
|
|
EN 61000-4-5
|
Designation
|
Conducted interferences
|
Standards/regulations
|
EN 61000-4-6
|
Electrical isolation
|
Basic insulation according to EN 61010
|
Conformance/approvals
Designation
|
CE
|
Certificate
|
CE-compliant
|
Designation
|
UL, USA/Canada
|
Identification
|
UL 508 Recognized
|
|
Class I, Div. 2, Groups A, B, C, D T5
|
Designation
|
Shipbuilding approval
|
Certificate
|
DNV GL TAA000020N
|
Temperature
|
B
|
Humidity
|
B
|
Vibration
|
B
|
EMC
|
A
|
Enclosure
|
Required protection according to the Rules shall be provided upon installation on board
|
Environmental Product Compliance
REACh SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 50 years
|
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
|
ECLASS
ECLASS 10.0.1 |
27210120
|
ECLASS 11.0 |
27210120
|
ECLASS 4.0 |
27210100
|
ECLASS 4.1 |
27210100
|
ECLASS 5.0 |
27210100
|
ECLASS 5.1 |
27210100
|
ECLASS 6.0 |
27210100
|
ECLASS 7.0 |
27210120
|
ECLASS 9.0 |
27210120
|
ETIM
ETIM 4.0 |
EC002653
|
ETIM 6.0 |
EC002653
|
ETIM 7.0 |
EC002653
|
UNSPSC
UNSPSC 6.01 |
30211506
|
UNSPSC 7.0901 |
39121008
|
UNSPSC 11 |
39121008
|
UNSPSC 12.01 |
39121008
|
UNSPSC 13.2 |
39121008
|
UNSPSC 18.0 |
39121008
|
UNSPSC 19.0 |
39121008
|
UNSPSC 20.0 |
39121008
|
UNSPSC 21.0 |
39121008
|
|
File description
|