General information |
Product type designation |
DQ 32x24VDC/0.5A HF |
HW functional status |
FS01 |
Firmware version |
V1.0.0 |
Product function |
● I&M data |
Yes; I&M0 to I&M3 |
Engineering with |
● STEP 7 TIA Portal configurable/integrated as of version |
V13 SP1 / - |
● PROFIBUS as of GSD version/GSD revision |
V1.0 / V5.1 |
● PROFINET as of GSD version/GSD revision |
V2.3 / - |
Operating mode |
● DQ |
Yes |
● DQ with energy-saving function |
No |
● PWM |
No |
● Oversampling |
No |
● MSO |
Yes |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes; through internal protection with 7 A per group |
Input current |
Current consumption, max. |
60 mA |
Output voltage |
Rated value (DC) |
24 V |
Power |
Power available from the backplane bus |
1.1 W |
Power loss |
Power loss, typ. |
3.5 W |
Digital outputs |
Type of digital output |
Transistor |
Number of digital outputs |
32 |
Current-sourcing |
Yes |
Short-circuit protection |
Yes; Clocked electronically |
● Response threshold, typ. |
1 A |
Limitation of inductive shutdown voltage to |
L+ (-53 V) |
Controlling a digital input |
Yes |
Switching capacity of the outputs |
● with resistive load, max. |
0.5 A |
● on lamp load, max. |
5 W |
Load resistance range |
● lower limit |
48 Ω |
● upper limit |
12 kΩ |
Output voltage |
● for signal "1", min. |
L+ (-0.8 V) |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "1" permissible range, max. |
0.5 A |
● for signal "0" residual current, max. |
0.5 mA |
Output delay with resistive load |
● "0" to "1", max. |
100 µs |
● "1" to "0", max. |
500 µs |
Parallel switching of two outputs |
● for logic links |
Yes |
● for uprating |
No |
● for redundant control of a load |
Yes |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
0.5 Hz; According to IEC 60947-5-1, DC-13 |
● on lamp load, max. |
10 Hz |
Total current of the outputs |
● Current per channel, max. |
0.5 A; see additional description in the manual |
● Current per group, max. |
4 A; see additional description in the manual |
● Current per module, max. |
16 A; see additional description in the manual |
Cable length |
● shielded, max. |
1 000 m |
● unshielded, max. |
600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
Yes |
Execution and activation time (TCO), min. |
70 µs |
Bus cycle time (TDP), min. |
250 µs |
Interrupts/diagnostics/status information |
Diagnostics function |
Yes |
Substitute values connectable |
Yes |
Alarms |
● Diagnostic alarm |
Yes |
Diagnostic messages |
● Monitoring the supply voltage |
Yes |
● Wire-break |
Yes |
● Short-circuit |
Yes |
● Group error |
Yes |
Diagnostics indication LED |
● RUN LED |
Yes; Green LED |
● ERROR LED |
Yes; Red LED |
● Monitoring of the supply voltage (PWR-LED) |
Yes; Green LED |
● Channel status display |
Yes; Green LED |
● for channel diagnostics |
Yes; Red LED |
● for module diagnostics |
Yes; Red LED |
Potential separation |
Potential separation channels |
● between the channels |
No |
● between the channels, in groups of |
8 |
● between the channels and backplane bus |
Yes |
Isolation |
Isolation tested with |
707 V DC (type test) |
Decentralized operation |
Prioritized startup |
Yes |
Dimensions |
Width |
35 mm |
Height |
147 mm |
Depth |
129 mm |
Weights |
Weight |
280 g |
last modified: |