Pilt on illustreeriv
|
Mõõtetrafo A82, 250AAC D27mm, output 4..20mA, LED, cv 10..40VDC, Carlo Gavazzi Kood:
A82-20250
Hind
€ 171,00
/tk
(€ 212,04 /tk KM-ga)
Tootja
:
|
Saadavus:
14 päeva
|
Kaal:
0.315 kg/tk
|
Maht:
0.0001 m3/tk
|
|
|
|
|
Overview
True RMS AC current metering transformer for direct connection to a PLC or monitoring relay. Available input current ranges are 0..25AAC, 0..50AAC, 0..100AAC, 0..250AAC, 0..500AAC with current or voltage output options.
Input Specifications
|
Input current ranges
|
0..25AAC, 0..50AAC, 0..100AAC, 0..250AAC, 0..500AAC
|
|
Maximum continuous current
|
600AAC
|
|
Maximum overload current
|
3000AAC for 30s
|
|
Rated insulation voltage
|
1000VAC RMS
|
|
Overvoltage category
|
IV according to IEC 60664
|
|
Dielectric voltage
|
6kVAC RMS
|
|
Rated impulse withstand voltage
|
12kV
|
Output Specifications
|
Output options
|
0..20mADC source, 4..20mADC sink, 0..10VDC
|
|
Power supply for current output
|
10..40VDC
|
|
Power supply for voltage output
|
18..40VDC
|
|
Output tolerance
|
±2% of full scale@50Hz
|
|
Frequency range
|
40Hz..1kHz
|
|
Maximum output current
|
30mADC
|
|
Maximum output voltage
|
15VDC
|
|
Minimum output load
|
10kΩ
|
General Specifications
|
Power ON delay
|
<2s
|
|
Reaction time
|
<200ms
|
|
Power indication
|
Green LED
|
|
Degree of protection
|
IP40
|
|
Pollution degree
|
3 according to IEC 60664
|
|
Operating temperature
|
-20..50°C
|
|
Relative humidity
|
5..95% non-condensing
|
|
Dimensions
|
95x67.5x20mm
|
|
Housing material
|
PC/ABS
|
|
Flammability rating
|
UL94 HB
|
|
Connection cable
|
2m
|
|
Approval
|
cURus
|
|
CE marking
|
Yes
|
Installation
Mount the transformer to a panel with screws. Connect the cable wires to the appropriate PLC or monitoring relay input, connect the power supply, then draw the measured conductor through the central opening.
|
|
|
|