e-Elit - juhtiv
elektri- ja automaatikatarvikute
online hulgimüük
Klienditeenindus E-R 9-17
Helista: +372 622 9119
Est En
Elit shopping basket
Tooteid: Maksumus:
0
€ 0,00
    search
Logi sisse
Kasutajatunnus/e-post:

Parool:

Näita kõiki kategooriaid
Ei leidnud sobilikku toodet?
Head pakkumised!
Kilbikarbik TransCab, 120Lx60K, A6/6, 2m/pc, hall
Kilbikarbik TransCab, 120Lx60K, A6/6, 2m/pc, hall



Näita laos
Näita km-ga hindu
Mõõtetrafo A82, 250AAC D27mm, output 4..20mA, LED, cv 10..40VDC, Carlo Gavazzi
Pilt on illustreeriv
Mõõtetrafo A82, 250AAC D27mm, output 4..20mA, LED, cv 10..40VDC, Carlo Gavazzi
Kood: A82-20250
Hind
€ 171,00  /tk
(€ 212,04 /tk KM-ga)
Tootja :
Saadavus:
14 päeva
Kaal:
0.315 kg/tk
Maht:
0.0001 m3/tk
Kogus (tk):
Plus sign Minus sign
 

Overview
True RMS AC current metering transformer for direct connection to a PLC or monitoring relay. Available input current ranges are 0..25AAC, 0..50AAC, 0..100AAC, 0..250AAC, 0..500AAC with current or voltage output options.
Input Specifications
Input current ranges 0..25AAC, 0..50AAC, 0..100AAC, 0..250AAC, 0..500AAC
Maximum continuous current 600AAC
Maximum overload current 3000AAC for 30s
Rated insulation voltage 1000VAC RMS
Overvoltage category IV according to IEC 60664
Dielectric voltage 6kVAC RMS
Rated impulse withstand voltage 12kV
Output Specifications
Output options 0..20mADC source, 4..20mADC sink, 0..10VDC
Power supply for current output 10..40VDC
Power supply for voltage output 18..40VDC
Output tolerance ±2% of full scale@50Hz
Frequency range 40Hz..1kHz
Maximum output current 30mADC
Maximum output voltage 15VDC
Minimum output load 10kΩ
General Specifications
Power ON delay <2s
Reaction time <200ms
Power indication Green LED
Degree of protection IP40
Pollution degree 3 according to IEC 60664
Operating temperature -20..50°C
Relative humidity 5..95% non-condensing
Dimensions 95x67.5x20mm
Housing material PC/ABS
Flammability rating UL94 HB
Connection cable 2m
Approval cURus
CE marking Yes
Installation
Mount the transformer to a panel with screws. Connect the cable wires to the appropriate PLC or monitoring relay input, connect the power supply, then draw the measured conductor through the central opening.
 
 
Elit OÜ | e-post: elit@elit.ee | +372 622 9119 | 2021 ©


 