Pilt on illustreeriv
|
Volume Flow Meter PremasReg 7161-U/W Display, volume flow, differential pressure, filter monitoring, fill level, range 10..100% adj., output 0..10V 1CO, clean air media -20..50°C, K 1..3000, LCD+BL, 3-wire, 24VAC/DC, IP65, S+S Regeltechnik Kood:
1302-7161-4161-200
Hind
€ 293,10
/tk
(€ 357,58 /tk KM-ga)
Tootja
:
Saadavus:
14 päeva
|
Kaal:
0.0315 kg/tk
|
|
|
|
|
|
Volume Flow Meter PremasReg 7161-U/W Display, volume flow ?differential pressure ?filter monitoring ?fill level, range 10..100% adj., output 0..10V 1CO, clean air media -20..50°C, K 1..3000, LCD+BL, 3-wire, 24VAC/DC, IP65, S+S RegeltechnikPREMASREG 7161-U/W
Item No. 1302-7161-4161-200
EAN 4 251325 612850
The electronic pressure sensor and switch PREMASREG® 716x is equipped with measuring functions for volume flow, differential pressure, filter monitoring and liquid level detection based on pressure measurement in clean air. The devices are fitted with one switching output, one continuous output and one backlit display for setting the switchpoint and displaying the ACTUAL values. The piezo-resistive measuring element guarantees a high degree of reliability and accuracy. This pressure sensor is used in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for level measurement or for triggering frequency converters. The medium measured is air (non-precipitating), or other gaseous non-aggressive, non-combustible media. It has a manual zero point pushbutton and an offset potentiometer for final value correction. Fine adjustment by the user is possible at any time. Parameter entry is menu-based and is easy to perform using three buttons with the help of the display. A connection set ASD-06 (2 m connection hose, two pressure nipples, screws) is included in the scope of supply.
Voltage supply |
24 V AC ⁄ DC (± 10 %) and 15...36 V DC |
Power consumption |
< 1.5 VA ⁄ 24 V DC, < 2.8 VA ⁄ 24 V AC |
Load resistance |
RL > 5 kOhm
|
Output signal |
0 -10 V 1 changeover contact (24 V), 1 A ohmic load |
Measuring function |
Volume flow, differential pressure,
filter monitoring, fill level (adjustable)
|
Measuring ranges |
10...100% (adjustable)
|
Media temperature |
–20...+50 °C |
Pressure connection |
4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm),
metal pressure connection nozzles
|
Type of pressure |
differential pressure |
Accuracy |
(1000 Pa): ± 5 Pa compared to the calibrated reference device
|
Above- ⁄ below-pressure |
max. ± 10000 Pa |
Medium |
clean air and
non-aggressive, non-combustible gases
|
Signal filtering |
switchable 1 s ⁄ 10 s
and small value suppression < 1 %
|
Signal hysteresis |
± 1 % or final value (pressure) 10 Pa ⁄ 50 Pa |
Electrical connection |
3-wire connection 0.14 - 1.5 mm², via plug-in screw terminal
|
Enclosure |
plastic, UV-stabilised, material polyamide,
30 % glass-globe reinforced,
with quick-locking screws
(slotted ⁄ Phillips head - combination),
colour traffic white (similar to RAL 9016),
enclosure cover for display is transparent !
|
Cable gland |
M 20 x 1.5; including strain relief |
Dimensions |
126 x 90 x 50 mm (Tyr 2) |
Sum of Linearity+hysteresis |
< ± 1 % of final value |
Temperature drift values |
± 0.1 % ⁄ °C |
Air humidity |
< 95 % r. H., non-precipitating air |
Protection class |
III (according to EN 60 730) |
Protection type |
IP 65 (according to EN 60 529) |
Standards |
CE conformity,
according to EMC directive 2014 ⁄ 30 ⁄ EU,
according to EN 61326-1, according to EN 61326-2-3
|
Features |
Display with illumination, three-line,
cutout approx. 70 x 40 mm (W x H),
for displaying the volume flow, differential pressure,
contamination degree or level
and for setting the switchpoint, K factor, measuring range limits
and other settings
|
K factor |
1 to 3000(adjustable)
|
Units |
m³ ⁄ s, m³ ⁄ min, m³ ⁄ h, l ⁄ s, l ⁄ min, l ⁄ h, %, cm(adjustable)
|
Max. value displayed |
999999 |
|
|
|
|