Power Supply 1606-XL, N+1 redundancy input 100..120/200..240VAC| man. select 240..375VDC, output 240W 10A 24..28VDC, out test plug, Allen-Bradley Kood:
1606-XL240E
€ 375,10
/tk
(€ 457,62 /tk KM-ga)
Tootja
:
Saadavus:
Laos
|
Kaal:
1.12 kg/tk
|
Maht:
0.0042 m3/tk
|
|
|
|
|
Power Supply 10A 240W 240VAC/ 24..28VDC, Allen-Bradley
Features
Rated outputs between 60…960 W (2.5…40 A at 24V DC)
Multiple output voltages available
Multiple single and three-phase inputs available for global applications
Buffer modules provide a short boost function, buffering load currents during typical main faults, switching events or load peaks
Redundancy modules provide a means for managing dual power supplies for back-up power
1606-XL Standard Switched Mode Power Supplies
Quick mounting and connecting, innovative DIN-Rail mount, smallest in class
UL Listed NEC Class 2; Class 1, Div. 2; Semi F47; ODVA Approved
Low inrush current limiting
PFC Active or Passive
Wide range input; auto select input
Superior overload design (continuous current, no hiccup)
NEC Class 2 'Limited Power' options
Selectable operating mode (single/parallel)
Superior efficiency and temperature rating
Special Modules
Brownout buffer, DC to DC converter, N+1 redundancy, DC UPS
Standards Compliance
World-wide Certifications
cULus, CE, C-Tick
NEC Class 2
SEMI F47 Compatible
Class 1 Div. 2 (T3A)
ABS/GL/RINA (Marine)
How to Select a Bulletin 1606 Power Supply
The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply to start high inrush loads.
Steps to size a Power Supply
Determine the "Average" continuous current of the load and the typicalinrush current.
Select a power supply where the rated load is at/or below the current of the device and the Peak Current is less than the short-circuit rating of the power supply.
Notes:
PowerBoost will deliver up to 25% additional current continuously at 40 °C or less.
ReservePower will deliver 150% of rated current for up to 5 s.
Example:
Application: Single Phase 120V input, 24V output, 5 A continuous current @ 35 °C, with 7.5 A inrush current.
Certifications:
CE, UL508 (cULus Listed), UL1950 (cURus), Safety standards = IEC/EN 60950, EN 50178, EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, EMC standards = EN 61000-3-2 (A14), EN 50081-1
|
Please see product data sheet Downloadable files.
|
|
|
|
|
|