Pilt on illustreeriv
|
Repeater Power Supply MACX MCR-SL-RPSSI-2I-SP, Phoenix Kood:
2924838
Hind
€ 284,10
/tk
(€ 346,60 /tk KM-ga)
Tootja
:
Saadavus:
küsi tarneaega
|
Kaal:
0.2428 kg/tk
|
Maht:
0.0002 m3/tk
|
|
|
|
|
Repeater Power Supply MACX MCR-SL-RPSSI-2I-SP, PhoenixNote
Utilization restriction
|
EMC: class A product, see manufacturer's declaration in the download area
|
Dimensions
Width
|
12.5 mm
|
Height
|
116 mm
|
Depth
|
114.5 mm
|
Ambient conditions
Ambient temperature (operation)
|
-20 °C ... 60 °C (Any mounting position)
|
|
-20 °C ... 70 °C (any mounting position, module distance 5 mm, MTBF reduction factor 2.5, not assessed by UL)
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Maximum altitude
|
≤ 2000 m
|
Permissible humidity (operation)
|
10 % ... 95 % (non-condensing)
|
Noise immunity
|
EN 61000-6-2
|
Input data
Signal input
|
Repeater power supply operation
|
Current input signal
|
4 mA ... 20 mA
|
Transmitter supply voltage
|
> 21.5 V (20 mA)
|
|
> 21 V (23 mA)
|
Underload/overload signal range
|
0 mA ... 24 mA (Extended transmission range for diagnostics)
|
Signal input
|
Signal conditioner operation
|
Current input signal
|
0 mA ... 20 mA
|
|
4 mA ... 20 mA
|
Voltage drop
|
< 3.9 V (in input isolating amplifier operation)
|
Underload/overload signal range
|
0 mA ... 24 mA (Extended transmission range for diagnostics)
|
Output data
Signal output
|
Repeater power supply operation
|
Current output signal
|
4 mA ... 20 mA (active)
|
|
0 mA ... 20 mA
|
Load/output load current output
|
< 450 Ω (20 mA)
|
|
< 380 Ω (23 mA)
|
Output ripple
|
< 20 mVrms
|
Output behavior in the event of an error
|
0 mA (Cable break in the input)
|
|
≥ 23 mA (Cable short-circuit in the input)
|
Signal output
|
Signal conditioner operation
|
Current output signal
|
0 mA ... 20 mA (active)
|
|
4 mA ... 20 mA (active)
|
Load/output load current output
|
< 450 Ω (20 mA)
|
|
< 380 Ω (23 mA)
|
Output ripple
|
< 20 mVrms
|
Output behavior in the event of an error
|
0 mA (Cable break in the input)
|
|
0 mA (Cable short-circuit in the input)
|
Power supply
Designation
|
Repeater power supply operation
|
Nominal supply voltage
|
24 V DC
|
Supply voltage range
|
19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
|
Max. current consumption
|
< 75 mA (24 V DC / 20 mA)
|
Power dissipation
|
< 1.45 W (24 V DC / 20 mA)
|
Designation
|
Signal conditioner operation
|
Nominal supply voltage range
|
19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
|
Max. current consumption
|
< 46 mA (24 V DC / 20 mA)
|
Power dissipation
|
< 1.2 W (24 V DC / 20 mA)
|
Connection data
Connection method
|
Push-in connection
|
Stripping length
|
8 mm
|
Conductor cross section solid
|
0.2 mm² ... 1.5 mm²
|
Conductor cross section flexible
|
0.2 mm² ... 1.5 mm²
|
Conductor cross section AWG
|
24 ... 16
|
General
No. of channels
|
1
|
Maximum transmission error
|
< 0.1 % (of final value)
|
Transmission error, typical
|
< 0.05 % (of final value)
|
Maximum temperature coefficient
|
< 0.01 %/K
|
Step response (10-90%)
|
1.3 ms (for jump 4 mA ... 20 mA, typical)
|
Status display
|
Green LED (PWR supply voltage)
|
Electromagnetic compatibility
|
Conformance with EMC directive
|
Interference emission
|
EN 61000-6-4
|
Housing material
|
PA 6.6-FR
|
Color
|
gray
|
Designation
|
Input/output/power supply
|
Rated insulation voltage
|
300 Vrms
|
Test voltage
|
2.5 kV AC (50 Hz, 1 min.)
|
Insulation
|
Safe isolation in accordance with IEC/EN 61010-1
|
Overvoltage category
|
II
|
Degree of pollution
|
2
|
Designation
|
Output 1/output 2
|
Test voltage
|
1.5 kV AC (50 Hz, 1 min.)
|
Data communication (bypass)
HART function
|
Yes
|
Protocols supported
|
HART
|
EMC data
Designation
|
Electromagnetic RF field
|
Standards/regulations
|
EN 61000-4-3
|
Typical deviation from the measuring range final value
|
3 %
|
Designation
|
Fast transients (burst)
|
Standards/regulations
|
EN 61000-4-4
|
Typical deviation from the measuring range final value
|
3 %
|
Designation
|
Conducted interferences
|
Standards/regulations
|
EN 61000-4-6
|
Typical deviation from the measuring range final value
|
3 %
|
Standards and Regulations
Electromagnetic compatibility
|
Conformance with EMC directive
|
Noise emission
|
EN 61000-6-4
|
Designation
|
Electromagnetic RF field
|
Standards/regulations
|
EN 61000-4-3
|
|
EN 61000-4-4
|
Designation
|
Conducted interferences
|
Standards/regulations
|
EN 61000-4-6
|
Conformance/approvals
Designation
|
CE
|
Certificate
|
CE-compliant
|
Additional text
|
and EN 61326-1
|
Designation
|
ATEX
|
Identification
|
II 3 G Ex nA IIC T4 Gc X
|
Designation
|
UL, USA/Canada
|
Identification
|
UL 508 Listed
|
|
UL 61010 Listed
|
|
Class I, Div. 2, Groups A, B, C, D T4
|
|
Class I, Zone 2, Groups IIC, IIB, IIA T4
|
Designation
|
UL, USA/Canada
|
Identification
|
UL 61010 Listed
|
|
Class I, Div. 2, Groups A, B, C, D T4
|
|
Class I, Zone 2, Group IIC T4
|
Designation
|
Shipbuilding approval
|
Identification
|
C, EMC2
|
Certificate
|
DNV GL TAA000020C
|
Designation
|
Safety Integrity Level (SIL, IEC 61508)
|
Identification
|
2
|
Temperature
|
B
|
Humidity
|
B
|
Vibration
|
A
|
EMC
|
A
|
Enclosure
|
Required protection according to the Rules shall be provided upon installation on board
|
Environmental Product Compliance
REACh SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 50 years
|
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
|
ECLASS
ECLASS 10.0.1 |
27210120
|
ECLASS 11.0 |
27210120
|
ECLASS 4.0 |
27210100
|
ECLASS 4.1 |
27210100
|
ECLASS 5.0 |
27210100
|
ECLASS 5.1 |
27210100
|
ECLASS 6.0 |
27210100
|
ECLASS 7.0 |
27210120
|
ECLASS 9.0 |
27210120
|
ETIM
ETIM 4.0 |
EC002653
|
ETIM 6.0 |
EC002653
|
ETIM 7.0 |
EC002653
|
UNSPSC
UNSPSC 6.01 |
30211506
|
UNSPSC 7.0901 |
39121008
|
UNSPSC 11 |
39121008
|
UNSPSC 12.01 |
39121008
|
UNSPSC 13.2 |
39121008
|
UNSPSC 18.0 |
39121008
|
UNSPSC 19.0 |
39121008
|
UNSPSC 20.0 |
39121008
|
UNSPSC 21.0 |
39121008
|
|
File description
|
File type
|
Download link
|
|
|
|
|
|
|
|
|