Twilight Sensor PhotasGard® AHKF-U, outdoor, ranges: 0..0.5/1/2/5/20/60kLux, output 0-10 V, polyamid, sv 24VAC/DC, IP65, S+S Regeltechnik, greyPHOTASGARD® AHKF-U
Item No. 1601-1111-1000-000
EAN 4 251325 613611
The light intensity sensor⁄twilight sensor PHOTASGARD® AHKF, with six switchable measuring ranges (six devices in one) measures the luminous intensity and is used to control luminaries, lighting systems, Venetian blinds and canvas blinds, etc., to monitor lighting conditions at workplaces, in greenhouses, storage halls, workshops, corridors, in outdoor areas, in industrial halls, in offices as well as in residential and business facilities, for daylight-dependant constant light control, as light intensity or twilight sensor and to control sunshade equipment avoiding unnecessary heating-up of rooms. It therefore minimizes your variety of types and stock keeping while covering a greater range of universal applications. The sensor used was specifically adapted to the sensitivity of the human eye. Its greatest sensitivity is in the range of 350 nm to 820 nm. Therefore, with its special filter, the sensor is ideally suited to exposure measurement of daylight and ⁄ or for measuring artificial light of high colour temperature (similar to sunlight).
Voltage supply |
24 V AC (± 20 %) and 15…36 V DC |
Power consumption |
< 1 W at 24 V DC; < 2 VA at 24 V AC |
Load resistance |
RL > 5 kOhm
|
Output |
0 -10 V (2- or 3-wire connection) |
Sensor |
light sensor |
Measuring ranges |
multi-range switching(via DIP switches)
with 6 switchable measuring ranges
0...500 Lux ⁄ 1 kLux ⁄ 2 kLux ⁄ 5 kLux ⁄ 20 kLux ⁄ 60 kLux
(other individual ranges optional, e. g. 100 kLux)
|
Measuring error |
< 5 % of final value |
Ambient temperature |
–30...+70 °C |
Electrical connection |
0.14 - 1.5 mm²
via terminal screws on circuit board
|
Enclosure |
plastic, UV-stabilised, material polyamide,
30 % glass-globe reinforced,
with quick-locking screws
(slotted ⁄ Phillips head - combination),
colour traffic white (similar to RAL 9016),
enclosure cover for display is transparent !
|
Enclosure dimensions |
72 x 64 x 43.3 mm (Tyr 1 with Display) |
Cable gland |
2x M 12 x 1.5 (Y-adapter); with strain relief,
exchangeable, max. inner diameter 6 mm
|
Dimensions |
72 x 64 x 43.3 mm (Tyr 1 with Display) |
Installation |
on-wall |
Protection class |
III (according to EN 60 730) |
Protection type |
IP 65 (according to EN 60 529) |
Standards |
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014 ⁄ 30 ⁄ EU
|
|