Image is illustrative
|
Safety Compact Block Input Module Guard I/O, 32-ch., 85mA 19.2..28.8VDC, TS35, Allen-Bradley Code:
1791DS-IB16
Price (indicative)
€545.20
/pc
(€665.14 /pc with VAT)
Manufacturer
:
Availability:
21 days
|
Weight:
0.71 kg/pc
|
Volume:
0.003 m3/pc
|
|
|
|
|
Safety Compact Block Input Module Guard I/O, 32-ch., 85mA 19.2..28.8VDC, TS35, Allen-Bradley
DESCRIPTIONS
-
Guard I/O™ Safety Compact Block Input Module, Number Of Channels: 32 (16 Input, 16 Test Output), Input: Safety Input - Voltage On-State Input: 11 VDC, Current On-State Input: 3.3 MA, Voltage Off-State Input: 5 VDC, Current Off-State: 1.3 MA, Pulse Test Output - Pulse Test Output Current: 0.7 A, Residual Voltage: 1.2 V, Output Leakage Current: 0.1 MA, Current: 25 MA, Voltage Rating: 19.2 - 28.8 VDC, Current Rating: Communication Current Consumption: 85 MA At 24 VDC, Isolation: 50 V (Continuous), Basic Insulation Type, Tested At 800 VDC For 60 SEC, Between Network And Input Channels, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 -2000 MHZ, 10 V/M With 200 Hz 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 Hz 50% Pulse 100% AM At 1890 MHZ, 1 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ, Connection Cables: 22 - 16 AWG Solid/Stranded Copper Wire, Communication: Devicenet, Mounting: DIN Rail, Length: 6.7 IN, Width: 2.9 IN, Height: 3.1 IN, Temperature Rating: -4 To 140 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% (Non-Condensing), Vibration: 5 G At 10 - 500 HZ, Shock - Operating: 30 G, Non-Operating: 50 G, Response Time: Input Reaction Time: 16.2 MS + Set Values Of On/Off Delays, Output Type: Current Sinking/Source, Surge Transient Immunity: Plus/Minus 1 KV Line-Line (DM) And Plus/Minus 2 KV Line-Earth (CM) On Power Ports, Plus/Minus 1 KV Line-Line (DM) And Plus/Minus 2 KV Line-Earth (CM) On Signal Ports, Plus/Minus 2 KV Line-Earth (CM) On Communication Ports, Standard/Approvals: C/US UL listed, CE-EMC, C-tick, GOST_R, KCC certified, TÜV certified
SPECIFICATIONS
-
-
Item Name: Safety Compact Block Input Module
-
Sub Brand: Guard I/O™
-
Number Of Channels: 32 (16 Input, 16 Test Output)
-
Input: Safety Input - Voltage On-State Input: 11 VDC, Current On-State Input: 3.3 MA, Voltage Off-State Input: 5 VDC, Current Off-State: 1.3 MA, Pulse Test Output - Pulse Test Output Current: 0.7 A, Residual Voltage: 1.2 V, Output Leakage Current: 0.1 MA, Current: 25 MA
-
Voltage Rating: 19.2 - 28.8 VDC
-
Current Rating: Communication Current Consumption: 85 MA At 24 VDC
-
Isolation: 50 V (Continuous), Basic Insulation Type, Tested At 800 VDC For 60 SEC, Between Network And Input Channels
-
Enclosure: Open Type
-
Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 -2000 MHZ, 10 V/M With 200 Hz 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 Hz 50% Pulse 100% AM At 1890 MHZ, 1 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ
-
Connection Cables: 22 - 16 AWG Solid/Stranded Copper Wire
-
Communication: Devicenet
-
Mounting: DIN Rail
-
Length: 6.7 IN
-
Width: 2.9 IN
-
Height: 3.1 IN
-
Temperature Rating: -4 To 140 DEG F
-
Environmental Conditions: Relative Humidity: 5 - 95% (Non-Condensing), Vibration: 5 G At 10 - 500 HZ, Shock - Operating: 30 G, Non-Operating: 50 G
-
Response Time: Input Reaction Time: 16.2 MS + Set Values Of On/Off Delays
-
Output Type: Current Sinking/Source
-
Surge Transient Immunity: Plus/Minus 1 KV Line-Line (DM) And Plus/Minus 2 KV Line-Earth (CM) On Power Ports, Plus/Minus 1 KV Line-Line (DM) And Plus/Minus 2 KV Line-Earth (CM) On Signal Ports, Plus/Minus 2 KV Line-Earth (CM) On Communication Ports
FEATURES
-
- Standards: C/US UL listed, CE-EMC, C-tick, GOST_R, KCC certified, TÜV certified
|
File description
|
File type
|
Download link
|
|
|
|
"
Spec Sheet
|
.pdf
|
Download link
|
|
|
|
|
|
|
|