Image is illustrative
|
Solenoid Driver KFD2-SL2-Ex1.LK, 1-ch. isolated barrier, DO 45mA 11.2VDC, non-polarized logic input, fault indication output, -20..60°C, LFD, ATEX, SIL2, 24VDC PR, Pepperl+Fuchs Code:
200542
Price (indicative)
€144.00
/pc
(€175.68 /pc with VAT)
Manufacturer
:
Availability:
ask for dd
|
Weight:
0.15 kg/pc
|
Volume:
0.0003 m3/pc
|
|
|
|
|
Solenoid Driver KFD2-SL2-Ex1.LK, 1-ch. isolated barrier, DO 45mA 11.2VDC, non-polarized logic input, fault indication output, -20..60°C, LFD, ATEX, SIL2, 24VDC PR, Pepperl+FuchsSolenoid Driver KFD2-SL2-Ex1.LK
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Output 45 mA at 11.2 V DC
- Logic input, non-polarized
- Fault indication output
- Line fault detection (LFD)
- Up to SIL 2 acc. to IEC 61508
Datasheet excerpt: Technical data of KFD2-SL2-Ex1.LK
General specifications |
Signal type | Digital Output |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 19 ... 30 V DC |
Power dissipation | max. 1.5 W |
Power consumption | max. 2 W at 45 mA output current |
Input |
Connection side | control side |
Connection | terminals 7, 8 |
Input current | approx. 3 mA |
Signal level | 1-signal: 16 ... 30 V DC 0-signal: 0 ... 5 V DC |
Output |
Connection side | field side |
Output I | |
| Connection | terminals 1+, 2- or 3- |
| Internal resistor | 270 Ω |
| Current | max. 45 mA |
| Voltage | min. 11.2 V |
| Open loop voltage | min. 23.5 V |
| Output signal | These values are valid for the rated operating voltage 19 ... 30 V DC. |
| Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
| Line fault detection | signal at short-circuit RB < 50 Ω, lead breakage RB > 10 kΩ ; test current < 650 µA |
Output II | fault signal |
| Connection | terminals 10, 11, 12 , non-intrinsically safe |
| Contact loading | 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load |
| Mechanical life | 2 x 107 switching cycles |
| Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility | NE 21:2007 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | ZELM 99 ATEX 0015 |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
Certificate | TÜV 02 ATEX 1820 X |
| Marking | II 3G Ex nA nC IIC T4 Gc |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 50303:2000 |
International approvals |
CSA approval | |
| Control drawing | 116-0362 |
IECEx approval | IECEx ZLM 14.0001 |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
|
|
|
|
|