General information |
Product type designation |
DQ 4x24 ... 230 V AC/2 A ST |
HW functional status |
from FS04 |
Firmware version |
V1.0 |
● FW update possible |
Yes |
usable BaseUnits |
BU type B1 |
Color code for module-specific color identification plate |
CC41 |
Product function |
● I&M data |
Yes; I&M0 to I&M3 |
Engineering with |
● STEP 7 TIA Portal configurable/integrated as of version |
V13 / V13 |
● STEP 7 configurable/integrated as of version |
V5.5 SP3 / - |
● PROFIBUS as of GSD version/GSD revision |
GSD Revision 5 |
● PROFINET as of GSD version/GSD revision |
GSDML V2.3 |
Operating mode |
● DQ |
Yes |
● DQ with energy-saving function |
No |
● PWM |
No |
● Oversampling |
No |
● MSO |
No |
Supply voltage |
Rated value (AC) |
230 V |
permissible range, lower limit (AC) |
20.4 V |
permissible range, upper limit (AC) |
264 V |
Input current |
Current consumption (rated value) |
11.5 mA |
Output voltage |
Rated value (AC) |
230 V; 24V AC to 230V AC |
Power loss |
Power loss, typ. |
9 W; Active power, load voltage 230 V, all outputs loaded with 2 A, 50 Hz |
Address area |
Address space per module |
● Address space per module, max. |
1 byte; + 1 byte for QI information |
● Inputs |
1 byte; With QI |
● Outputs |
1 byte |
Digital outputs |
Type of digital output |
Triac with zero point detection |
Number of digital outputs |
4 |
Current-sinking |
No |
Current-sourcing |
Yes |
Short-circuit protection |
No; When using BU type B1, a miniature, quick-response fuse with 10 A tripping current must be provided |
Controlling a digital input |
Yes |
Size of motor starters according to NEMA, max. |
5 |
Switching capacity of the outputs |
● with resistive load, max. |
2 A |
● on lamp load, max. |
100 W |
Output voltage |
● for signal "1", min. |
20.4 V |
Output current |
● for signal "1" rated value |
2 A |
● for signal "1" permissible range, min. |
10 mA |
● for signal "1" permissible range, max. |
2 A |
● for signal "0" residual current, max. |
460 µA |
Output delay with resistive load |
● "0" to "1", max. |
10 ms |
● "1" to "0", max. |
10 ms |
Parallel switching of two outputs |
● for logic links |
No |
● for uprating |
No |
● for redundant control of a load |
Yes |
Switching frequency |
● with resistive load, max. |
10 Hz |
● with inductive load, max. |
0.5 Hz; Higher frequencies are possible, see Equipment Manual / Product Information |
● on lamp load, max. |
1 Hz |
Total current of the outputs |
● Current per channel, max. |
2 A |
● Current per module, max. |
8 A |
Total current of the outputs (per module) |
horizontal installation |
— up to 40 °C, max. |
8 A |
— up to 50 °C, max. |
6 A |
— up to 60 °C, max. |
4 A |
vertical installation |
— up to 30 °C, max. |
8 A |
— up to 40 °C, max. |
6 A |
— up to 50 °C, max. |
4 A |
Cable length |
● shielded, max. |
1 000 m |
● unshielded, max. |
600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Diagnostics function |
No |
Substitute values connectable |
Yes |
Alarms |
● Diagnostic alarm |
No |
Diagnostic messages |
● Monitoring the supply voltage |
No |
● Wire-break |
No |
● Short-circuit |
No |
● Group error |
Yes |
Diagnostics indication LED |
● Monitoring of the supply voltage (PWR-LED) |
Yes; green PWR LED |
● Channel status display |
Yes; Green LED |
● for channel diagnostics |
No |
● for module diagnostics |
Yes; green/red DIAG LED |
Potential separation |
Potential separation channels |
● between the channels |
No |
● between the channels and backplane bus |
Yes |
● between the channels and the power supply of the electronics |
No |
Isolation |
Isolation tested with |
2 545 V DC/2 s (routine test) |
Dimensions |
Width |
20 mm |
Height |
73 mm |
Depth |
58 mm |
Weights |
Weight, approx. |
50 g |
last modified: |
11/10/2018 |