General information |
Product type designation |
AQ 4xU/I ST |
HW functional status |
From FS07 |
usable BaseUnits |
BU type A0, A1 |
Color code for module-specific color identification plate |
CC00 |
Product function |
● I&M data |
Yes; I&M0 to I&M3 |
● Output range scalable |
No |
Engineering with |
● STEP 7 TIA Portal configurable/integrated as of version |
V11 SP2 / V13 |
● STEP 7 configurable/integrated as of version |
V5.5 SP3 / - |
● PCS 7 configurable/integrated as of version |
V8.1 SP1 |
● PROFIBUS as of GSD version/GSD revision |
One GSD file each, Revision 3 and 5 and higher |
● PROFINET as of GSD version/GSD revision |
GSDML V2.3 |
Operating mode |
● Oversampling |
No |
● MSO |
No |
CiR – Configuration in RUN |
Reparameterization possible in RUN |
Yes |
Calibration possible in RUN |
No |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
19.2 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes |
Input current |
Current consumption, max. |
150 mA |
Power loss |
Power loss, typ. |
1.5 W |
Address area |
Address space per module |
● Address space per module, max. |
8 byte; + 1 byte for QI information |
Analog outputs |
Number of analog outputs |
4 |
Voltage output, short-circuit current, max. |
45 mA |
Cycle time (all channels), min. |
5 ms |
Analog output with oversampling |
No |
Output ranges, voltage |
● 0 to 10 V |
Yes; 15 bit |
● 1 V to 5 V |
Yes; 13 bit |
● -5 V to +5 V |
Yes; 15 bit incl. sign |
● -10 V to +10 V |
Yes; 16 bit incl. sign |
Output ranges, current |
● 0 to 20 mA |
Yes; 15 bit |
● -20 mA to +20 mA |
Yes; 16 bit incl. sign |
● 4 mA to 20 mA |
Yes; 14 bit |
Connection of actuators |
● for voltage output two-wire connection |
Yes |
● for voltage output four-wire connection |
Yes |
● for current output two-wire connection |
Yes |
Load impedance (in rated range of output) |
● with voltage outputs, min. |
2 kΩ |
● with voltage outputs, capacitive load, max. |
1 µF |
● with current outputs, max. |
500 Ω |
● with current outputs, inductive load, max. |
1 mH |
Destruction limits against externally applied voltages and currents |
● Voltages at the outputs |
30 V |
Cable length |
● shielded, max. |
1 000 m; 200 m for voltage output |
Analog value generation for the outputs |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit |
Settling time |
● for resistive load |
0.1 ms |
● for capacitive load |
1 ms |
● for inductive load |
0.5 ms |
Errors/accuracies |
Linearity error (relative to output range), (+/-) |
0.03 % |
Temperature error (relative to output range), (+/-) |
0.005 %/K |
Crosstalk between the outputs, min. |
-50 dB |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) |
0.05 % |
Operational error limit in overall temperature range |
● Voltage, relative to output range, (+/-) |
0.5 % |
● Current, relative to output range, (+/-) |
0.5 % |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to output range, (+/-) |
0.3 % |
● Current, relative to output range, (+/-) |
0.3 % |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Diagnostics function |
Yes |
Substitute values connectable |
Yes |
Alarms |
● Diagnostic alarm |
Yes |
Diagnostic messages |
● Monitoring the supply voltage |
Yes |
● Wire-break |
Yes |
● Short-circuit |
Yes |
● Group error |
Yes |
● Overflow/underflow |
Yes |
Diagnostics indication LED |
● Monitoring of the supply voltage (PWR-LED) |
Yes; Green PWR LED |
● Channel status display |
Yes; Green LED |
● for channel diagnostics |
No |
● for module diagnostics |
Yes; green/red DIAG LED |
Potential separation |
Potential separation channels |
● between the channels |
No |
● between the channels and backplane bus |
Yes |
● between the channels and the power supply of the electronics |
Yes |
Isolation |
Isolation tested with |
707 V DC (type test) |
Ambient conditions |
Ambient temperature during operation |
● horizontal installation, min. |
-30 °C |
● horizontal installation, max. |
60 °C; Observe derating |
● vertical installation, min. |
-30 °C |
● vertical installation, max. |
50 °C; Observe derating |
Altitude during operation relating to sea level |
● Installation altitude above sea level, max. |
2 000 m; On request: Installation altitudes greater than 2 000 m |
Dimensions |
Width |
15 mm |
Height |
73 mm |
Depth |
58 mm |
Weights |
Weight, approx. |
31 g |
last modified: |