Free-Standing Rack 19in, 42U 600Wx2065Hx600D, toughened glass front door, removable side panels, cable entry on the top, bottom, incl. adj. feet, castors, max. load 800kg, flatpack, grey
Free-Standing Rack 19in, 42U 600Wx2065Hx600D, toughened glass front door, removable side panels, cable entry on the top, bottom, incl. adj. feet, castors, max. load 800kg, flatpack, grey



Show stock items
Show price with local vat
KFD2-CRG2-1.D| Transmitter Power Supply, 1ch, input 2/3wire transm. ^2-wire current sources, output 0/4..20mA, 2RO, high/low alarm, LFD, SIL2, 24VDC PR
Image is illustrative
KFD2-CRG2-1.D| Transmitter Power Supply, 1ch, input 2/3wire transm. ^2-wire current sources, output 0/4..20mA, 2RO, high/low alarm, LFD, SIL2, 24VDC PR
Code: 255621
Price (indicative)
€233.00  /pc
(€288.92 /pc with VAT)
Manufacturer :
Availability:
21 days
Weight:
0.315 kg/pc
Volume:
0.0006 m3/pc
Quantity (pc):
Plus sign Minus sign
 

 

Transmitter Power Supply KFD2-CRG2-1.D, 1-ch., input 2-/3-wire transm.?2-wire current sources, output 0/4..20mA, 2RO, high/low alarm, LFD, SIL2, 24VDC PR, Pepperl+Fuchs

Transmitter Power Supply KFD2-CRG2-1.D
  • 1-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • Input 2-wire and 3-wire transmitters and 2-wire current sources
  • Output 0/4 mA ... 20 mA
  • 2 relay contact outputs
  • Programmable high/low alarm
  • Linearization function (max 20 points)
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508/IEC 61511

Datasheet excerpt: Technical data of KFD2-CRG2-1.D

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 23+, 24-
Rated voltage20 ... 30 V DC
Rated currentapprox. 130 mA
Power dissipation2 W
Power consumption2.5 W
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Connectionterminals 1, 2, 3
Input I
Input signal0/4 ... 20 mA
Available voltage≥ 15 V at 20 mA
Open circuit voltage/short-circuit current24 V / 33 mA
Input resistance45 Ω (terminals 2, 3)
Line fault detectionbreakage I < 0.2 mA; short-circuit I > 22 mA
Output
Connection sidecontrol side
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
Output: analog terminals 8+, 7-
Output signal0 ... 20 mA or 4 ... 20 mA
Output I, IIsignal, relay
Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life5 x 107 switching cycles
Output IIISignal, analog
Current range0 ... 20 mA or 4 ... 20 mA
Open loop voltagemax. 24 V DC
Loadmax. 650 Ω
Fault signaldownscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Indicators/settings
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons
via PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
International approvals
UL approvalE223772
 
 