Image is illustrative
|
Relay REL-IR4/L-230AC/4X21, 10psc/pck, Phoenix Code:
2903688
Price (indicative)
€101.00
/pk
(€125.24 /pk with VAT)
Package 10pc, unit price
10.1EUR/pc
Manufacturer
:
Availability:
21 days
|
Weight:
0.0324 kg/pc
|
Volume:
0 m3/pc
|
|
|
|
|
Relay REL-IR4/L-230AC/4X21, 10psc/pck, PhoenixDimensions
Width
|
21.2 mm
|
Height
|
27.5 mm
|
Depth
|
35.6 mm
|
Ambient conditions
Ambient temperature (operation)
|
-40 °C ... 55 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Degree of protection
|
RT I
|
Coil side
Nominal input voltage UN
|
230 V AC
|
Input voltage range in reference to UN
|
|
Mains frequency
|
50/60 Hz
|
Typical input current at UN
|
6.5 mA
|
Typical response time
|
5 ms ... 15 ms (depending on phase relation)
|
Typical release time range
|
5 ms ... 20 ms (depending on phase relation)
|
Status display
|
Yellow LED
|
Power dissipation for nominal condition
|
1.5 W
|
Contact side
Contact type
|
4 changeover contacts
|
Type of switch contact
|
Single contact
|
Contact material
|
AgNi
|
Maximum switching voltage
|
250 V AC/DC
|
Minimum switching voltage
|
5 V (At 24 mA)
|
Min. switching current
|
5 mA (at 24 V)
|
Maximum inrush current
|
16 A (20 ms, N/O contacts)
|
Limiting continuous current
|
6 A
|
Interrupting rating (ohmic load) max.
|
144 W (at 24 V DC)
|
|
124 W (at 48 V DC)
|
|
108 W (at 60 V DC)
|
|
52 W (at 110 V DC)
|
|
48 W (at 220 V DC)
|
|
1500 VA (for 250 V AC)
|
Switching capacity min.
|
0.12 W
|
Switching capacity
|
2 A (at 24 V, DC13)
|
|
0.22 A (at 120 V, DC13)
|
|
0.11 A (at 250 V, DC13)
|
|
1.5 A (at 24 V, AC15)
|
|
1.5 A (at 120 V, AC15)
|
|
1 A (at 240 V, AC15)
|
General
Test voltage
|
2.5 kVrms (50 Hz, 1 min., winding/contact)
|
|
2 kVrms (50 Hz, 1 min., changeover contact/changeover contact)
|
Operating mode
|
100% operating factor
|
Mechanical service life
|
approx. 2x 107 cycles
|
Service life, electrical
|
see diagram
|
Mounting position
|
any
|
Connection data
Connection method
|
Plug connection
|
Standards and Regulations
Connection in acc. with standard
|
CSA
|
Standards/regulations
|
IEC 60664
|
|
IEC 61810
|
Rated insulation voltage
|
250 V AC
|
Rated surge voltage
|
2.5 kV
|
Insulation
|
Basic insulation
|
Pollution degree
|
2
|
Overvoltage category
|
II
|
Conformance/approvals
Designation
|
Corrosive gas test
|
Identification
|
ISA-S71.04. G3 Harsh Group
|
|
EN 60068-2-60
|
Environmental Product Compliance
China RoHS
|
Environmentally Friendly Use Period = 50 years
|
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
|
ECLASS
ECLASS 10.0.1 |
27371601
|
ECLASS 11.0 |
27371601
|
ECLASS 4.0 |
27371100
|
ECLASS 4.1 |
27371100
|
ECLASS 5.0 |
27371600
|
ECLASS 5.1 |
27371600
|
ECLASS 6.0 |
27371600
|
ECLASS 7.0 |
27371601
|
ECLASS 9.0 |
27371601
|
ETIM
ETIM 2.0 |
EC001437
|
ETIM 3.0 |
EC001437
|
ETIM 4.0 |
EC001437
|
ETIM 6.0 |
EC001437
|
ETIM 7.0 |
EC001437
|
UNSPSC
UNSPSC 6.01 |
30211916
|
UNSPSC 7.0901 |
39121515
|
UNSPSC 11 |
39121515
|
UNSPSC 12.01 |
39121515
|
UNSPSC 13.2 |
39122334
|
UNSPSC 18.0 |
39122334
|
UNSPSC 19.0 |
39122334
|
UNSPSC 20.0 |
39122334
|
UNSPSC 21.0 |
39122334
|
|
File description
|