Control Desk ZBA, 800Wx1000Hx400D, front door, upper panel, TS35, gas springs, mounting plate, adj. cable entry, doors w. ø3mm double bar closing system, CE/UL, IP55 IK10, NEMA12, grey
Control Desk ZBA, 800Wx1000Hx400D, front door, upper panel, TS35, gas springs, mounting plate, adj. cable entry, doors w. ø3mm double bar closing system, CE/UL, IP55 IK10, NEMA12, grey



Show stock items
Show price with local vat
Siplus S7-300, SM331 8AE -25..70°C, w. conformal coating, based on 6ES7331-1KF02-0AB0, optically isolated, 8AI, 13bit resolution, U/I/resistance/PT100/NI100/NI1000/LG-NI1000, PTC/KTY, 66ms module update, 40pin
Image is illustrative
Siplus S7-300, SM331 8AE -25..70°C, w. conformal coating, based on 6ES7331-1KF02-0AB0, optically isolated, 8AI, 13bit resolution, U/I/resistance/PT100/NI100/NI1000/LG-NI1000, PTC/KTY, 66ms module update, 40pin
Code: 6AG1331-1KF02-7AB0
Price (indicative)
€458.70  /pc
(€568.79 /pc with VAT)
Manufacturer :
Availability:
21 days
Weight:
0.294 kg/pc
Volume:
0.001 m3/pc
Quantity (pc):
Plus sign Minus sign
 

 

Siplus S7-300, SM331 8AE -25..70°C, w. conformal coating, based on 6ES7331-1KF02-0AB0, optically isolated, 8AI, 13bit resolution, U/I/resistance/PT100/NI100/NI1000/LG-NI1000, PTC/KTY, 66ms module update, 40pin, Siemens

Input current
from backplane bus 5 V DC, max. 90 mA
Power loss
Power loss, typ. 0.4 W
Analog inputs
Number of analog inputs 8
● For resistance measurement 8
permissible input voltage for voltage input (destruction limit), max. 30 V; 12 V continuous, 30 V for max. 1 s
permissible input current for current input (destruction limit), max. 40 mA
Input ranges
● Voltage Yes
● Current Yes
● Thermocouple No
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) 100 kΩ
● 1 V to 5 V Yes
● Input resistance (1 V to 5 V) 100 kΩ
● 1 V to 10 V No
● -1 V to +1 V Yes
● Input resistance (-1 V to +1 V) 100 kΩ
● -10 V to +10 V Yes
● Input resistance (-10 V to +10 V) 100 kΩ
● -2.5 V to +2.5 V No
● -250 mV to +250 mV No
● -5 V to +5 V Yes
● Input resistance (-5 V to +5 V) 100 kΩ
● -50 mV to +50 mV Yes
● Input resistance (-50 mV to +50 mV) 100 kΩ
● -500 mV to +500 mV Yes
● Input resistance (-500 mV to +500 mV) 100 kΩ
● -80 mV to +80 mV No
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 100 Ω
● -10 mA to +10 mA No
● -20 mA to +20 mA Yes
● Input resistance (-20 mA to +20 mA) 100 Ω
● -3.2 mA to +3.2 mA No
● 4 mA to 20 mA Yes
● Input resistance (4 mA to 20 mA) 100 Ω
Input ranges (rated values), thermocouples
● Type B No
● Type C No
● Type E No
● Type J No
● Type K No
● Type L No
● Type N No
● Type R No
● Type S No
● Type T No
● Type U No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Ni 100 Yes; Standard/climate
● Input resistance (Ni 100) 100 MΩ
● Ni 1000 Yes
● Input resistance (Ni 1000) 100 MΩ
● LG-Ni 1000 Yes; Standard/climate
● Input resistance (LG-Ni 1000) 100 MΩ
● Ni 120 No
● Ni 200 No
● Ni 500 No
● Pt 100 Yes; Standard/climate
● Input resistance (Pt 100) 100 MΩ
● Pt 1000 No
● Pt 200 No
● Pt 500 No
Input ranges (rated values), resistors
● 0 to 150 ohms No
● 0 to 300 ohms No
● 0 to 600 ohms Yes
● Input resistance (0 to 600 ohms) 100 MΩ
● 0 to 6000 ohms Yes
● Input resistance (0 to 6000 ohms) 100 MΩ
Characteristic linearization
● parameterizable Yes
— for resistance thermometer yes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.; LG-Ni1000 standard/air con.
Cable length
● shielded, max. 200 m; max. 50 m at 50 mV
Analog value generation for the inputs
Measurement principle integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 13 bit
● Integration time, parameterizable Yes; 60 / 50 ms
● Basic conversion time (ms) 66 / 55 ms
● Interference voltage suppression for interference frequency f1 in Hz 50 / 60 Hz
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer Yes; with external supply
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection Yes
● for resistance measurement with four-wire connection Yes
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.6 %; ±0.6 % (±5 V, 10 V, 1 to 5 V, 0 to 10 V); ±0.5 % (±50 mV, 500 mV, 1 V) @ 0 ... +60 °C; ±0.7 % (±5 V, 10 V, 1 to 5 V, 0 to 10 V); ±0.6 % (±50 mV, 500 mV, 1 V) @ -25 ... +70 °C
● Current, relative to input range, (+/-) 0.5 %; @ 0 ... +60 °C; ±0.6% @ -25 ... +70 °C; ±20 mA, 0 to 20 mA, 4 to 20 mA
● Resistance, relative to input range, (+/-) 0.5 %; @ 0 ... +60 °C; 0.6% @ -25 ... +70 °C; 0 to 6 kohm, 0 to 600 kohm
● Resistance thermometer, relative to input range, (+/-) 1 Kelvin (Pt100, Ni100, climate; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climate); 1.2 Kelvin (Pt100, Ni100, standard) @ 0 ... +60 °C; 1.2 Kelvin (Pt100, Ni100, climate; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climate); 1.4 Kelvin (Pt100, Ni100, standard) @ -25 ... +70 °C
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.4 %; 0.4% (±5 V, 10 V, 1 to 5 V, 0 to 10 V); 0.3% (±50 mV, 500 mV, 1 V)
● Current, relative to input range, (+/-) 0.3 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
● Resistance, relative to input range, (+/-) 0.3 %; 0 to 6 kohms, 0 to 600 kohms
● Resistance thermometer, relative to input range, (+/-) 1 Kelvin (Pt100, Ni100, standard); 0.8 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climatic)
Interrupts/diagnostics/status information
Diagnostic functions No
Alarms
● Diagnostic alarm No
● Limit value alarm No
Diagnostic messages
● Diagnostic information readable No
Diagnostics indication LED
● Group error SF (red) No
Potential separation
Potential separation analog inputs
● between the channels and backplane bus Yes
Isolation
Isolation tested with 500 V DC
Standards, approvals, certificates
CE mark Yes
UL approval Yes; File E239877
FM approval Yes; CofC 3028431
RCM (formerly C-TICK) Yes
KC approval Yes
EAC (formerly Gost-R) Yes
Railway application
● EN 50121-4 No
● EN 50155 No
Ambient conditions
Ambient temperature during operation
● min. -25 °C
● max. 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Altitude during operation relating to sea level
● Ambient air temperature-barometric pressure-altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-2-38, max. 100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3 Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3 Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— to mechanically active substances according to EN 60721-3-3 Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Connection method
required front connector 40-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 117 mm
Weights
Weight, approx. 250 g
last modified: 11/17/2017
 
 