| Supply voltage |
| Load voltage L+ |
| ● Rated value (DC) |
24 V |
| ● Reverse polarity protection |
Yes |
| Input current |
| from load voltage L+ (without load), max. |
48 mA |
| from backplane bus 3.3 V DC, max. |
10 mA |
| Output voltage |
| Power supply to the transmitters |
| ● present |
Yes |
| ● short-circuit proof |
Yes |
| Power loss |
| Power loss, typ. |
1.2 W |
| Address area |
| Address space per module |
| ● Address space per module, max. |
4 byte |
| Analog inputs |
| Number of analog inputs |
2 |
| permissible input current for current input (destruction limit), max. |
50 mA |
| Cycle time (all channels) max. |
0.5 ms; 0.5 ms for 2 channels without noise suppression, 18 / 21 ms per channel with noise suppression |
| Input ranges (rated values), currents |
| ● -20 mA to +20 mA |
Yes |
| ● 4 mA to 20 mA |
Yes |
| Cable length |
| ● shielded, max. |
200 m |
| Analog value generation for the inputs |
| Measurement principle |
Sigma Delta |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. |
16 bit |
| ● Interference voltage suppression for interference frequency f1 in Hz |
60 / 50 Hz / no |
| ● Conversion time (per channel) |
0.04 ms; Without noise suppression 17/20 ms per channel with error |
| Smoothing of measured values |
| ● parameterizable |
Yes; In 4 stages: 1x, 4x, 16x, 32x cycle time |
| ● Step: None |
Yes; 1x |
| ● Step: low |
Yes; 4x |
| ● Step: Medium |
Yes; 16x |
| ● Step: High |
Yes; 32x |
| Encoder |
| Connection of signal encoders |
| ● for current measurement as 2-wire transducer |
|
| — Burden of 2-wire transmitter, max. |
750 Ω |
| Errors/accuracies |
| Linearity error (relative to input range), (+/-) |
0.03 % |
| Temperature error (relative to input range), (+/-) |
0.003 %/K |
| Crosstalk between the inputs, min. |
-100 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) |
0.01 % |
| Operational error limit in overall temperature range |
| ● Current, relative to input range, (+/-) |
0.1 %; 0.2% without interference frequency suppression |
| Basic error limit (operational limit at 25 °C) |
| ● Current, relative to input range, (+/-) |
0.05 %; 0.1% without interference frequency suppression |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
| ● Series mode interference (peak value of interference < rated value of input range), min. |
90 dB |
| ● Common mode interference (USS < 2.5 V) , min. |
100 dB |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) |
Yes |
| Interrupts/diagnostics/status information |
| Alarms |
| ● Hardware interrupt |
Yes |
| Diagnostic messages |
| ● Wire-break |
Yes; Measuring range 4 to 20 mA only |
| ● Group error |
Yes |
| ● Overflow/underflow |
Yes |
| Diagnostics indication LED |
| ● Group error SF (red) |
Yes |
| Parameter |
| Remark |
12 bytes, 4 bytes in compatibility mode |
| Diagnostics wire break |
Disable / enable |
| Measurement type/range |
deactivated / ±20 mA / 4 to 20 mA |
| Group diagnostics |
Disable / enable |
| Overflow/underflow |
Disable / enable |
| Potential separation |
| Potential separation analog inputs |
| ● between the channels |
No; however, increased permissible potential difference between the inputs. |
| ● between the channels and backplane bus |
Yes |
| ● Between the channels and load voltage L+ |
Yes |
| Dimensions |
| Width |
15 mm |
| Height |
81 mm |
| Depth |
52 mm |
| Weights |
| Weight, approx. |
45 g |
| last modified: |
06/07/2019 |