| Input current |
| from backplane bus 5 V DC, max. |
90 mA |
| Power loss |
| Power loss, typ. |
0.4 W |
| Analog inputs |
| Number of analog inputs |
8 |
| ● For resistance measurement |
8 |
| permissible input voltage for voltage input (destruction limit), max. |
30 V; 12 V continuous, 30 V for max. 1 s |
| permissible input current for current input (destruction limit), max. |
40 mA |
| Input ranges |
| ● Voltage |
Yes |
| ● Current |
Yes |
| ● Thermocouple |
No |
| ● Resistance thermometer |
Yes |
| ● Resistance |
Yes |
| Input ranges (rated values), voltages |
| ● 0 to +10 V |
Yes |
| ● Input resistance (0 to 10 V) |
100 kΩ |
| ● 1 V to 5 V |
Yes |
| ● Input resistance (1 V to 5 V) |
100 kΩ |
| ● 1 V to 10 V |
No |
| ● -1 V to +1 V |
Yes |
| ● Input resistance (-1 V to +1 V) |
100 kΩ |
| ● -10 V to +10 V |
Yes |
| ● Input resistance (-10 V to +10 V) |
100 kΩ |
| ● -2.5 V to +2.5 V |
No |
| ● -250 mV to +250 mV |
No |
| ● -5 V to +5 V |
Yes |
| ● Input resistance (-5 V to +5 V) |
100 kΩ |
| ● -50 mV to +50 mV |
Yes |
| ● Input resistance (-50 mV to +50 mV) |
100 kΩ |
| ● -500 mV to +500 mV |
Yes |
| ● Input resistance (-500 mV to +500 mV) |
100 kΩ |
| ● -80 mV to +80 mV |
No |
| Input ranges (rated values), currents |
| ● 0 to 20 mA |
Yes |
| ● Input resistance (0 to 20 mA) |
100 Ω |
| ● -10 mA to +10 mA |
No |
| ● -20 mA to +20 mA |
Yes |
| ● Input resistance (-20 mA to +20 mA) |
100 Ω |
| ● -3.2 mA to +3.2 mA |
No |
| ● 4 mA to 20 mA |
Yes |
| ● Input resistance (4 mA to 20 mA) |
100 Ω |
| Input ranges (rated values), thermocouples |
| ● Type B |
No |
| ● Type C |
No |
| ● Type E |
No |
| ● Type J |
No |
| ● Type K |
No |
| ● Type L |
No |
| ● Type N |
No |
| ● Type R |
No |
| ● Type S |
No |
| ● Type T |
No |
| ● Type U |
No |
| ● Type TXK/TXK(L) to GOST |
No |
| Input ranges (rated values), resistance thermometer |
| ● Cu 10 |
No |
| ● Ni 100 |
Yes; Standard/climate |
| ● Input resistance (Ni 100) |
100 MΩ |
| ● Ni 1000 |
Yes |
| ● Input resistance (Ni 1000) |
100 MΩ |
| ● LG-Ni 1000 |
Yes; Standard/climate |
| ● Input resistance (LG-Ni 1000) |
100 MΩ |
| ● Ni 120 |
No |
| ● Ni 200 |
No |
| ● Ni 500 |
No |
| ● Pt 100 |
Yes; Standard/climate |
| ● Input resistance (Pt 100) |
100 MΩ |
| ● Pt 1000 |
No |
| ● Pt 200 |
No |
| ● Pt 500 |
No |
| Input ranges (rated values), resistors |
| ● 0 to 150 ohms |
No |
| ● 0 to 300 ohms |
No |
| ● 0 to 600 ohms |
Yes |
| ● Input resistance (0 to 600 ohms) |
100 MΩ |
| ● 0 to 6000 ohms |
Yes |
| ● Input resistance (0 to 6000 ohms) |
100 MΩ |
| Thermocouple (TC) |
| Temperature compensation |
| — parameterizable |
No |
| — internal temperature compensation |
No |
| — external temperature compensation with compensations socket |
No |
| Characteristic linearization |
| ● parameterizable |
Yes |
| — for thermocouples |
No |
| — for resistance thermometer |
yes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.; LG-Ni1000 standard/air con. |
| Cable length |
| ● shielded, max. |
200 m; max. 50 m at 50 mV |
| Analog value generation for the inputs |
| Measurement principle |
integrating |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. |
13 bit |
| ● Integration time, parameterizable |
Yes; 60 / 50 ms |
| ● Basic conversion time (ms) |
66 / 55 ms |
| ● Interference voltage suppression for interference frequency f1 in Hz |
50 / 60 Hz |
| Encoder |
| Connection of signal encoders |
| ● for current measurement as 2-wire transducer |
Yes; with external supply |
| ● for current measurement as 4-wire transducer |
Yes |
| ● for resistance measurement with two-wire connection |
Yes |
| ● for resistance measurement with three-wire connection |
Yes |
| ● for resistance measurement with four-wire connection |
Yes |
| Errors/accuracies |
| Operational error limit in overall temperature range |
| ● Voltage, relative to input range, (+/-) |
0.6 %; ±0.6 % (±5 V, 10 V, 1 to 5 V, 0 to 10 V); ±0.5 % (±50 mV, 500 mV, 1 V) |
| ● Current, relative to input range, (+/-) |
0.5 %; ±20 mA, 0 to 20 mA, 4 to 20 mA |
| ● Resistance, relative to input range, (+/-) |
0.5 %; 0 to 6 kohms, 0 to 600 kohms |
| ● Resistance thermometer, relative to input range, (+/-) |
1 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climatic); 1.2 Kelvin (Pt100, Ni100, standard) |
| Basic error limit (operational limit at 25 °C) |
| ● Voltage, relative to input range, (+/-) |
0.4 %; 0.4% (±5 V, 10 V, 1 to 5 V, 0 to 10 V); 0.3% (±50 mV, 500 mV, 1 V) |
| ● Current, relative to input range, (+/-) |
0.3 %; ±20 mA, 0 to 20 mA, 4 to 20 mA |
| ● Resistance, relative to input range, (+/-) |
0.3 %; 0 to 6 kohms, 0 to 600 kohms |
| ● Resistance thermometer, relative to input range, (+/-) |
1 Kelvin (Pt100, Ni100, standard); 0.8 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climatic) |
| Interrupts/diagnostics/status information |
| Diagnostic functions |
No |
| Alarms |
| ● Diagnostic alarm |
No |
| ● Limit value alarm |
No |
| Diagnostic messages |
| ● Diagnostic information readable |
No |
| Diagnostics indication LED |
| ● Group error SF (red) |
No |
| Potential separation |
| Potential separation analog inputs |
| ● between the channels and backplane bus |
Yes |
| Isolation |
| Isolation tested with |
500 V DC |
| Connection method |
| required front connector |
40-pin |
| Dimensions |
| Width |
40 mm |
| Height |
125 mm |
| Depth |
117 mm |
| Weights |
| Weight, approx. |
250 g |
| last modified: |
11/21/2017 |