| Supply voltage |
| Load voltage L+ |
| ● Rated value (DC) |
24 V |
| ● Reverse polarity protection |
Yes |
| Input current |
| from load voltage L+ (without load), max. |
240 mA |
| from backplane bus 5 V DC, max. |
100 mA |
| Power loss |
| Power loss, typ. |
3 W |
| Analog inputs |
| Number of analog inputs |
8 |
| permissible input voltage for voltage input (destruction limit), max. |
75 V; 20 V DC permanent, 75 V DC for max. 1 s (duty factor 1:20) |
| Input ranges |
| ● Voltage |
No |
| ● Current |
No |
| ● Thermocouple |
Yes |
| ● Resistance thermometer |
No |
| ● Resistance |
No |
| Input ranges (rated values), voltages |
| ● 0 to +10 V |
No |
| ● 1 V to 5 V |
No |
| ● 1 V to 10 V |
No |
| ● -1 V to +1 V |
No |
| ● -10 V to +10 V |
No |
| ● -2.5 V to +2.5 V |
No |
| ● -250 mV to +250 mV |
No |
| ● -5 V to +5 V |
No |
| ● -50 mV to +50 mV |
No |
| ● -500 mV to +500 mV |
No |
| ● -80 mV to +80 mV |
No |
| Input ranges (rated values), currents |
| ● 0 to 20 mA |
No |
| ● -10 mA to +10 mA |
No |
| ● -20 mA to +20 mA |
No |
| ● -3.2 mA to +3.2 mA |
No |
| ● 4 mA to 20 mA |
No |
| Input ranges (rated values), thermocouples |
| ● Type B |
Yes |
| ● Type C |
Yes |
| ● Type E |
Yes |
| ● Type J |
Yes |
| ● Type K |
Yes |
| ● Type L |
Yes |
| ● Type N |
Yes |
| ● Type R |
Yes |
| ● Type S |
Yes |
| ● Type T |
Yes |
| ● Type U |
Yes |
| ● Type TXK/TXK(L) to GOST |
Yes |
| Input ranges (rated values), resistance thermometer |
| ● Cu 10 |
No |
| ● Ni 100 |
No |
| ● Ni 1000 |
No |
| ● LG-Ni 1000 |
No |
| ● Ni 120 |
No |
| ● Ni 200 |
No |
| ● Ni 500 |
No |
| ● Pt 100 |
No |
| ● Pt 1000 |
No |
| ● Pt 200 |
No |
| ● Pt 500 |
No |
| Input ranges (rated values), resistors |
| ● 0 to 150 ohms |
No |
| ● 0 to 300 ohms |
No |
| ● 0 to 600 ohms |
No |
| ● 0 to 6000 ohms |
No |
| Thermocouple (TC) |
| Temperature compensation |
| — parameterizable |
Yes |
| — internal temperature compensation |
Yes |
| — external temperature compensation with compensations socket |
Yes |
| — external temperature compensation with Pt100 |
Yes |
| Characteristic linearization |
| ● parameterizable |
Yes |
| — for thermocouples |
Type B, E, J, K, L, N, R, S. T, U, C |
| Cable length |
| ● shielded, max. |
100 m |
| Analog value generation for the inputs |
| Measurement principle |
integrating |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. |
16 bit; Two's complement |
| ● Integration time, parameterizable |
Yes |
| ● Basic conversion time (ms) |
Up to 4 channels: 10 ms per module, 5 channels upwards: 190 ms per module |
| ● Interference voltage suppression for interference frequency f1 in Hz |
400 / 60 / 50 Hz |
| Errors/accuracies |
| Operational error limit in overall temperature range |
| ● Voltage, relative to input range, (+/-) |
±1 K |
| Interrupts/diagnostics/status information |
| Diagnostic functions |
Yes; Parameterizable |
| Alarms |
| ● Diagnostic alarm |
Yes; Parameterizable per group |
| ● Limit value alarm |
Yes; Parameterizable |
| ● Hardware interrupt |
Yes; Parameterizable, channels 0 to 7 |
| Diagnostic messages |
| ● Diagnostic information readable |
Yes |
| Diagnostics indication LED |
| ● Group error SF (red) |
Yes |
| Potential separation |
| Potential separation analog inputs |
| ● between the channels and backplane bus |
Yes |
| Isolation |
| Isolation tested with |
500 V DC |
| Connection method |
| required front connector |
40-pin |
| Dimensions |
| Width |
40 mm |
| Height |
125 mm |
| Depth |
120 mm |
| Weights |
| Weight, approx. |
272 g |
| last modified: |
11/21/2017 |