Image is illustrative
|
Simatic S7-1500, Digital Input Module, 16DI 24VDC BA, sourcing input, 16-ch. in groups of 16, input delay 3.2ms, input type 3 (IEC 61131) Code:
6ES7521-1BH50-0AA0
Price (indicative)
€183.40
/pc
(€227.42 /pc with VAT)
Manufacturer
:
|
Availability:
28 days
|
Weight:
0.3003 kg/pc
|
Volume:
0.001 m3/pc
|
|
|
|
|
Simatic S7-1500, Digital Input Module, 16DI 24VDC BA, sourcing input, 16-ch. in groups of 16, input delay 3.2ms, input type 3 (IEC 61131), SiemensSIMATIC S7-1500, digital input module DI 16x24 V DC BA, sourcing input; 16 channels in groups of 16; Input delay 3.2 ms; Input type 3 (IEC 61131): Front connector (screw terminals or push-in) to be ordered separately
| General information |
| HW functional status |
FS01 |
| Firmware version |
V2.0.0 |
| ● FW update possible |
Yes |
| Product function |
| ● I&M data |
Yes; I&M0 to I&M3 |
| Engineering with |
| ● STEP 7 TIA Portal configurable/integrated as of version |
V12 / V12 |
| ● STEP 7 configurable/integrated as of version |
V5.5 SP3 / - |
| ● PROFIBUS as of GSD version/GSD revision |
V1.0 / V5.1 |
| ● PROFINET as of GSD version/GSD revision |
V2.3 / - |
| Operating mode |
| ● DI |
Yes |
| ● Counter |
No |
| ● MSI |
Yes |
| Supply voltage |
| permissible range, lower limit (DC) |
20.4 V |
| permissible range, upper limit (DC) |
28.8 V |
| Power |
| Power available from the backplane bus |
0.9 W |
| Power loss |
| Power loss, typ. |
2.8 W |
| Digital inputs |
| Number of digital inputs |
16 |
| Digital inputs, parameterizable |
No |
| Source/sink input |
m-reading |
| Input characteristic curve in accordance with IEC 61131, type 3 |
Yes |
| Input voltage |
| ● Rated value (DC) |
24 V |
| ● for signal "0" |
-5 to +30V |
| ● for signal "1" |
-11 to -30V |
| Input current |
| ● for signal "1", typ. |
4.5 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| — parameterizable |
No |
| — at "0" to "1", min. |
3 ms |
| — at "0" to "1", max. |
4 ms |
| — at "1" to "0", min. |
3 ms |
| — at "1" to "0", max. |
4 ms |
| for interrupt inputs |
| — parameterizable |
No |
| for technological functions |
| — parameterizable |
No |
| Cable length |
| ● shielded, max. |
1 000 m |
| ● unshielded, max. |
600 m |
| Encoder |
| Connectable encoders |
| ● 2-wire sensor |
Yes |
| — permissible quiescent current (2-wire sensor), max. |
1.5 mA |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) |
No |
| Interrupts/diagnostics/status information |
| Diagnostics function |
No |
| Alarms |
| ● Diagnostic alarm |
No |
| ● Hardware interrupt |
No |
| Diagnostic messages |
| ● Monitoring the supply voltage |
No |
| ● Wire-break |
No |
| ● Short-circuit |
No |
| Diagnostics indication LED |
| ● RUN LED |
Yes; Green LED |
| ● ERROR LED |
Yes; Red LED |
| ● Monitoring of the supply voltage (PWR-LED) |
No |
| ● Channel status display |
Yes; Green LED |
| ● for channel diagnostics |
No |
| ● for module diagnostics |
No |
| Potential separation |
| Potential separation channels |
| ● between the channels |
No |
| ● between the channels, in groups of |
16 |
| ● between the channels and backplane bus |
Yes |
| Isolation |
| Isolation tested with |
707 V DC (type test) |
| Standards, approvals, certificates |
| Suitable for safety functions |
No |
| Ambient conditions |
| Ambient temperature during operation |
| ● horizontal installation, min. |
0 °C |
| ● horizontal installation, max. |
60 °C |
| ● vertical installation, min. |
0 °C |
| ● vertical installation, max. |
40 °C |
| Decentralized operation |
| Prioritized startup |
Yes |
| Dimensions |
| Width |
35 mm |
| Height |
147 mm |
| Depth |
129 mm |
| Weights |
| Weight, approx. |
230 g |
| last modified: |
03/13/2019 |
|
|