General information |
HW functional status |
FS01 |
Firmware version |
V1.0.0 |
● FW update possible |
Yes |
Product function |
● I&M data |
Yes; I&M0 to I&M3 |
Engineering with |
● STEP 7 TIA Portal configurable/integrated as of version |
V13 SP1 / - |
● STEP 7 configurable/integrated as of version |
V5.5 SP3 / - |
● PROFIBUS as of GSD version/GSD revision |
V1.0 / V5.1 |
● PROFINET as of GSD version/GSD revision |
V2.3 / - |
Operating mode |
● DQ |
Yes |
● DQ with energy-saving function |
No |
● PWM |
No |
● Oversampling |
No |
● MSO |
Yes |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes |
Input current |
Current consumption, max. |
150 mA |
Output voltage |
Rated value (AC) |
230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC |
Power |
Power available from the backplane bus |
0.8 W |
Power loss |
Power loss, typ. |
5 W |
Digital outputs |
Type of digital output |
Relays |
Number of digital outputs |
16 |
Current-sinking |
Yes |
Current-sourcing |
Yes |
Digital outputs, parameterizable |
Yes |
Short-circuit protection |
No |
Controlling a digital input |
Yes |
Size of motor starters according to NEMA, max. |
5 |
Switching capacity of the outputs |
● on lamp load, max. |
50 W (230 V AC), 5 W (24 V DC) |
Output current |
● for signal "1" rated value |
2 A |
● for signal "1" permissible range, min. |
10 mA; 10 V |
● for signal "1" permissible range, max. |
2 A; thermal continuous current |
● for signal "0" residual current, max. |
0 A |
Parallel switching of two outputs |
● for logic links |
Yes |
● for uprating |
No |
● for redundant control of a load |
Yes |
Switching frequency |
● with resistive load, max. |
1 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
1 Hz |
Total current of the outputs |
● Current per channel, max. |
2 A; see additional description in the manual |
● Current per group, max. |
4 A; see additional description in the manual |
● Current per module, max. |
32 A; see additional description in the manual |
Relay outputs |
● Number of relay outputs |
16 |
● Rated supply voltage of relay coil L+ (DC) |
24 V |
● Current consumption of relays (coil current of all relays), typ. |
150 mA |
● external protection for relay outputs |
Miniature circuit breaker B10 / B16 |
● Contact connection (internal) |
No |
● Number of operating cycles, max. |
see additional description in the manual |
● Relay approved acc. to UL 508 |
No |
Switching capacity of contacts |
— with inductive load, max. |
2 A; see additional description in the manual |
— with resistive load, max. |
2 A; see additional description in the manual |
Cable length |
● shielded, max. |
1 000 m |
● unshielded, max. |
600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Diagnostics function |
Yes |
Substitute values connectable |
Yes |
Alarms |
● Diagnostic alarm |
Yes |
● Maintenance interrupt |
No |
Diagnostic messages |
● Monitoring the supply voltage |
Yes |
● Wire-break |
No |
● Short-circuit |
No |
Diagnostics indication LED |
● RUN LED |
Yes; Green LED |
● ERROR LED |
Yes; Red LED |
● Monitoring of the supply voltage (PWR-LED) |
Yes; Green LED |
● Channel status display |
Yes; Green LED |
● for channel diagnostics |
No |
● for module diagnostics |
Yes; Red LED |
Potential separation |
Potential separation channels |
● between the channels |
No |
● between the channels, in groups of |
2 |
● between the channels and backplane bus |
Yes |
● Between the channels and load voltage L+ |
Yes |
Permissible potential difference |
between different circuits |
250 V AC between the channels and the supply voltage L+; 250 V AC between the channels and the backplane bus; 500 V AC between the channels |
Isolation |
Isolation tested with |
Between channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test) |
Standards, approvals, certificates |
Suitable for safety functions |
No |
Ambient conditions |
Ambient temperature during operation |
● horizontal installation, min. |
0 °C |
● horizontal installation, max. |
60 °C |
● vertical installation, min. |
0 °C |
● vertical installation, max. |
40 °C |
Decentralized operation |
Prioritized startup |
Yes |
Dimensions |
Width |
35 mm |
Height |
147 mm |
Depth |
129 mm |
Weights |
Weight, approx. |
350 g |
last modified: |
06/03/2019 |