Image is illustrative
|
True RMS AC Current Transformer A82, 50AAC D27mm, output 4..20mA, LED, cv 10..40VDC, Carlo Gavazzi Code:
A82-2050
Price
€171.00
/pc
(€212.04 /pc with VAT)
Manufacturer
:
|
Availability:
14 days
|
Weight:
0.315 kg/pc
|
Volume:
0.0001 m3/pc
|
|
|
|
|
Overview
True RMS AC current metering transformer for measuring AC current and providing a standard analogue output for connection to a PLC or monitoring relay.
Features
|
Measurement principle
|
True RMS
|
|
Application
|
AC current interface for PLC or monitoring relay
|
|
Power indication
|
Green LED
|
|
Installation
|
Panel mounting with screws
|
Input Specifications
|
Current ranges
|
0..25AAC, 0..50AAC, 0..100AAC, 0..250AAC, 0..500AAC
|
|
Maximum continuous current
|
600AAC
|
|
Maximum overload current
|
3000AAC for 30s
|
|
Rated insulation voltage
|
1000VAC RMS
|
|
Overvoltage category
|
IV according to IEC 60664
|
|
Dielectric voltage
|
6kVAC RMS
|
|
Rated impulse withstand voltage
|
12kV
|
Output Specifications
|
Analogue outputs
|
0..20mADC, 4..20mADC, 0..10VDC
|
|
Power supply for current output
|
10..40VDC
|
|
Power supply for voltage output
|
18..40VDC
|
|
Output tolerance at 50Hz
|
±2% of full scale
|
|
Frequency range
|
40Hz..1kHz
|
|
Maximum output current
|
30mADC
|
|
Maximum output voltage
|
15VDC
|
General Specifications
|
Power ON delay
|
Less than 2s
|
|
Reaction time
|
Less than 200ms
|
|
Degree of protection
|
IP40
|
|
Pollution degree
|
3 according to IEC 60664
|
|
Operating temperature
|
-20..50°C
|
|
Relative humidity
|
5..95% non-condensing
|
|
Dimensions
|
95x67.5x20mm
|
|
Housing material
|
PC/ABS
|
|
Flammability rating
|
HB according to UL94
|
|
Connection cable length
|
2m
|
|
Approval
|
cURus
|
|
CE marking
|
Yes
|
|
|
|
|