Image is illustrative
|
Transducer P20, input 0..60mV, output 4..20mA, progr. PD14-0 ^eCon, sv 85..253VAC/DC Code:
P20-2159008
Price
€239.00
/pc
(€296.36 /pc with VAT)
Manufacturer
:
|
Availability:
21 days
|
Weight:
0.18 kg/pc
|
Volume:
0.0008 m3/pc
|
|
|
|
|
Overview
Programmable transducer for converting temperature, resistance, current, voltage and standard input signals into an isolated current or voltage analog output signal.
Features
Full galvanic isolation between the input, output and power supply.
Configurable input type, measurement averaging time and analog output scaling.
Automatic three-wire resistance compensation and thermocouple terminal temperature compensation.
Accuracy class 0.2.
Input Signals
|
Resistance thermometers
|
Pt100, Pt250, Pt500, Pt1000
|
|
Thermocouples
|
J, K, S, N
|
|
Resistance
|
0..4000Ω
|
|
DC current
|
-20..20mA, 0..20mA, 4..20mA, 0..5mA
|
|
DC voltage
|
-10..10V, -5..5V, 0..10V, 0..5V
|
|
DC millivoltage
|
-150..150mV, -60..60mV, 0..150mV, 0..60mV
|
Analog Outputs
|
Current output
|
0..20mA or 4..20mA
|
|
Current output load
|
≤500Ω
|
|
Voltage output
|
0..10V
|
|
Voltage output load
|
≥500Ω
|
Technical Data
|
Accuracy class
|
0.2
|
|
Supply voltage
|
85..253VAC/VDC, 45..65Hz
|
|
Alternative supply voltage
|
20..85VDC or 20..65VAC, 45..65Hz
|
|
Power consumption
|
<2VA
|
|
Dimensions
|
22.5x120x100mm
|
|
Housing protection
|
IP40
|
|
Terminal protection
|
IP20
|
|
Mounting
|
35mm DIN rail
|
Operating Conditions
|
Ambient temperature
|
-20..55°C
|
|
Storage temperature
|
-25..85°C
|
|
Relative humidity
|
<95%, without condensation
|
|
Preheating time
|
10min
|
|
Installation category
|
III
|
|
Pollution level
|
2
|
|
Maximum altitude
|
<2000m
|
|
|
|
Related products
|
|
|
|