Elit logo e-Elit - leading
electronic and automation component
online distributor
Est En
Elit shopping basket
Items: Total:
0
€0.00
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Mounting Plate Marina, 800Wx1000H, galvanized steel
Mounting Plate Marina, 800Wx1000H, galvanized steel



Show stock items
Show price with local vat
Surge Arrester V50-3+FS-275, T1+T2, Uc 275VAC, impulse current (10/350μs) Iimp 12.5kA, discharge current (8/20μs)| Imax 50kA ^In 20kA, Up ≤1.5kV, tA ≤25ns, FS 0.5A 250VAC/ 3A 30VDC| 1.5mm2, 2.5..25mm², TN-C, TÜV, CB, CE, MaxPro
Image is illustrative
Surge Arrester V50-3+FS-275, T1+T2, Uc 275VAC, impulse current (10/350μs) Iimp 12.5kA, discharge current (8/20μs)| Imax 50kA ^In 20kA, Up ≤1.5kV, tA ≤25ns, FS 0.5A 250VAC/ 3A 30VDC| 1.5mm2, 2.5..25mm², TN-C, TÜV, CB, CE, MaxPro
Code: V50-3-FS-275
Price
€85.30  /pc
(€105.77 /pc with VAT)
Manufacturer :
Availability:
In Stock
Weight:
0.4611 kg/pc
Volume:
0.0006 m3/pc
Wholesale qty:
36pc
Quantity (pc):
Plus sign Minus sign
 

Overview
Type 1+2 AC surge protection device with varistor voltage limiting technology, pluggable modules, thermal disconnection, status indication, and optional remote signalling.
Features
Type 1+2 AC surge protection device
Impulse/maximum discharge current [Iimp/Imax]: 12.5kA/50kA
Varistor voltage limiting technology with low residual voltage design
Pluggable design with internal thermal disconnection devices
Operating/fault indication with optional remote signal
Conforms to IEC 61643-11, EN 61643-11, GB/T 18802.11
Technology Parameters
AC working voltage [Un] 230VAC
Maximum continuous operating voltage [Uc] 275VAC
Temporary overvoltage test value TOV-5s [Ut] 335VAC
Temporary overvoltage test value TOV-120min [Ut] 440VAC
Nominal discharge current [8/20µs] [In] 20kA
Maximum discharge current [8/20µs] [Imax] 50kA
Impulse discharge current [10/350µs] [Iimp] 12.5kA
Voltage protection level [Up] ≤1.5kV
Short-circuit current rating [Isccr] 25kA
Response time [tA] ≤25ns
Thermal disconnection device Insertion
Maximum backup fuse 160..200A gG fuse
Mechanical Data
Wiring method Screw terminal 2.5..25mm², busbar compatible
Normal/fault display Green/Red
Remote signal Yes
Maximum remote signal load 0.5A 250VAC/ 3A 30VDC
Remote signal connection 1.5mm²
Installation 35mm DIN rail
Operating temperature range [Tu] -40..85°C
Protection level IP20
Enclosure material Thermoplastic material, UL94-V0
 
 
Elit OÜ | e-post: elit@elit.ee | +372 622 9119 | 2016 ©


 
X
 
X