Image is illustrative
|
Surge Arrester V50-4+FS-275, T1+T2, Uc 275VAC, impulse current (10/350μs) Iimp 12.5kA, discharge current (8/20μs)| Imax 50kA ^In 20kA, Up ≤1.5kV, tA ≤25ns, FS 0.5A 250VAC/ 3A 30VDC| 1.5mm2, 2.5..25mm², TN-S, TÜV, CB, CE, MaxPro Code:
V50-4-FS-275
Price
€108.00
/pc
(€133.92 /pc with VAT)
Manufacturer
:
|
Availability:
In Stock
|
Weight:
0.6143 kg/pc
|
Volume:
0.0007 m3/pc
|
Wholesale qty:
28pc
|
|
|
|
Overview
Type 1+2 AC surge protection device with varistor voltage limiting technology, pluggable modules, thermal disconnection, status indication, and optional remote signalling.
Features
Type 1+2 AC surge protection device
Impulse/maximum discharge current [Iimp/Imax]: 12.5kA/50kA
Varistor voltage limiting technology with low residual voltage design
Pluggable design with internal thermal disconnection devices
Operating/fault indication with optional remote signal
Conforms to IEC 61643-11, EN 61643-11, GB/T 18802.11
Technology Parameters
|
AC working voltage [Un]
|
230VAC
|
|
Maximum continuous operating voltage [Uc]
|
275VAC
|
|
Temporary overvoltage test value TOV-5s [Ut]
|
335VAC
|
|
Temporary overvoltage test value TOV-120min [Ut]
|
440VAC
|
|
Nominal discharge current [8/20µs] [In]
|
20kA
|
|
Maximum discharge current [8/20µs] [Imax]
|
50kA
|
|
Impulse discharge current [10/350µs] [Iimp]
|
12.5kA
|
|
Voltage protection level [Up]
|
≤1.5kV
|
|
Short-circuit current rating [Isccr]
|
25kA
|
|
Response time [tA]
|
≤25ns
|
|
Thermal disconnection device
|
Insertion
|
|
Maximum backup fuse
|
160..200A gG fuse
|
Mechanical Data
|
Wiring method
|
Screw terminal 2.5..25mm², busbar compatible
|
|
Normal/fault display
|
Green/Red
|
|
Remote signal
|
Yes
|
|
Maximum remote signal load
|
0.5A 250VAC/ 3A 30VDC
|
|
Remote signal connection
|
1.5mm²
|
|
Installation
|
35mm DIN rail
|
|
Operating temperature range [Tu]
|
-40..85°C
|
|
Protection level
|
IP20
|
|
Enclosure material
|