General information |
HW functional status |
FS04 |
Firmware version |
V2.2.0 |
● FW update possible |
Yes |
Product function |
● I&M data |
Yes; I&M0 to I&M3 |
Engineering with |
● STEP 7 TIA Portal configurable/integrated as of version |
V13 SP1 / - |
● STEP 7 configurable/integrated as of version |
V5.5 SP3 / - |
● PROFIBUS as of GSD version/GSD revision |
V1.0 / V5.1 |
● PROFINET as of GSD version/GSD revision |
V2.3 / - |
Operating mode |
● DI |
Yes |
● Counter |
Yes |
● Oversampling |
No |
● MSI |
Yes |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes |
Input current |
Current consumption, max. |
20 mA; with 24 V DC supply |
Power |
Power available from the backplane bus |
1.1 W |
Power loss |
Power loss, typ. |
2.6 W |
Digital inputs |
Number of digital inputs |
16 |
Digital inputs, parameterizable |
Yes |
Source/sink input |
P-reading |
Input characteristic curve in accordance with IEC 61131, type 3 |
Yes |
Digital input functions, parameterizable |
● Gate start/stop |
Yes |
● Freely usable digital input |
Yes |
● Counter |
|
— Number, max. |
2 |
— Counting frequency, max. |
3 kHz |
— Counting width |
32 bit |
— Counting direction up/down |
Up |
Input voltage |
● Rated value (DC) |
24 V |
● for signal "0" |
-30 to +5V |
● for signal "1" |
+11 to +30V |
Input current |
● for signal "1", typ. |
2.5 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable |
Yes; 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms |
— at "0" to "1", min. |
0.05 ms |
— at "0" to "1", max. |
20 ms |
— at "1" to "0", min. |
0.05 ms |
— at "1" to "0", max. |
20 ms |
for interrupt inputs |
— parameterizable |
Yes |
for technological functions |
— parameterizable |
Yes |
Cable length |
● shielded, max. |
1 000 m |
● unshielded, max. |
600 m |
Encoder |
Connectable encoders |
● 2-wire sensor |
Yes |
— permissible quiescent current (2-wire sensor), max. |
1.5 mA |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
Yes |
Filtering and processing time (TCI), min. |
80 µs; At 50 μs filter time |
Bus cycle time (TDP), min. |
250 µs |
Interrupts/diagnostics/status information |
Diagnostics function |
Yes |
Alarms |
● Diagnostic alarm |
Yes |
● Hardware interrupt |
Yes |
Diagnostic messages |
● Monitoring the supply voltage |
Yes |
● Wire-break |
Yes; to I < 350 µA |
● Short-circuit |
No |
Diagnostics indication LED |
● RUN LED |
Yes; Green LED |
● ERROR LED |
Yes; Red LED |
● Monitoring of the supply voltage (PWR-LED) |
Yes; Green LED |
● Channel status display |
Yes; Green LED |
● for channel diagnostics |
Yes; Red LED |
● for module diagnostics |
Yes; Red LED |
Potential separation |
Potential separation channels |
● between the channels |
No |
● between the channels, in groups of |
16 |
● between the channels and backplane bus |
Yes |
● between the channels and the power supply of the electronics |
No |
Isolation |
Isolation tested with |
707 V DC (type test) |
Standards, approvals, certificates |
Suitable for safety functions |
No |
Ambient conditions |
Ambient temperature during operation |
● horizontal installation, min. |
0 °C |
● horizontal installation, max. |
60 °C |
● vertical installation, min. |
0 °C |
● vertical installation, max. |
40 °C |
Decentralized operation |
Prioritized startup |
Yes |
Dimensions |
Width |
35 mm |
Height |
147 mm |
Depth |
129 mm |
Weights |
Weight, approx. |
240 g |
last modified: |
03/13/2019 |